In a block of flats in Torquay there is a service trunking that is open up through the building to each floor with Electrical isolators & consumer units. Following a Fire Risk Assessment (FRA) it was recommended that these should be isolated / compartmentalised and the doors upgraded to FD30(S) specification.
Following technical advice from specialist suppliers giving a method of achieving the recommendation of the FRA the following was fitted;-
- The service trunking was battoned out both top and bottom
- Where possible the wiring looms were pulled together and fitted with an intumescent wrap and secured with a stainless steel cable tie.
- The trunking was sealed with Fire Batt stopping with tight fits around the wiring looms and sealed with intumescent mastic.
Finally the doors upgraded to FD30(S) specification
See below.
Finally the doors upgraded to FD30(S) specification. See below.